Input
|
Input type
|
Capacitive humidity sensor & Pt 100 class A
|
Operating Range Suggestion
|
Temperature
|
0 ... 50°C(THS301)
- 40...+ 80°C(THS302 / 304 / 307)
|
Humidity
|
0 ... 100%RH
|
Output
|
Output
|
4 ... 20 mA / 0 ... 10 V / RS-485
|
Signal connection
|
3-wire
|
Display type
|
LCD Module with back light, double line character
|
Display range
|
Upon request, one decimal place
|
Height of character
|
5.56 mm
|
Linear Accuracy(at 25°C)
|
Temperature
|
±0.2°C±0.005°Cx tactual
|
Humidity
|
Nonlinear error : ±1.8%RH
Repeatability error : ±0.7%RH
|
Temp. influence
|
0.05%RH/°C
|
Load resistance
|
Current output : Max. 500 Ω
Voltage output : Min. 10 KΩ
|
Output calibration (ZERO & SPAN)
|
Software
|
Response time t90 (Temp. at+25°C)
|
<20 sec(Membrane filter)
<30 sec(Sintered filter)
|
Electrical
|
Power supply
|
DC 8 ... 35 V / AC 12 ... 30 V
|
Current consumption
|
DC 24 V : 60 mA / DC 12 V : 120
mA
AC 24 V : 140 mA / AC 12 V : 230 mA
|
Electrical connection
|
M12 connector with 2 m cable
or terminal(Cable gland)
|
Environment
|
Medium
|
Air
|
Operating Temp.
|
Housing : - 20 ... + 60°C
Housing with display : 0 ... 60°C
|
Operating humidity
|
Housing : 0 ... 95%(Non-condensing)
|
Proof Temp.
|
PC probe : Max.80°C
|
Cable
|
PVC cable : Max.80°C(Remote type)
|
Storage Temp.
|
- 25 ... + 60°C
|
Filter
|
Plastic membrane filter(Standard);Option
|
Certification
|
Certification
|
CE
|
Protection
|
IP rating
|
Housing : IP65;Probe : IP20
|
Electric protection
|
■ Reverse polarity ■ Over-voltage ■ Short-circuit
|
Installation
|
Installation
|
Wall type
Outdoor : Supporting plate (Standard)
Duct / Remote : Plastic flange (Standard)
|
Material
|
Housing
|
PC fire-proof class(PC-110)(UL94V-2)
|
Probe
|
PC fire-proof class(PC-110)
|